Bio-clean Operating Theater

Center of operating room is cleaned by clean air. You can choose horizontal airflow or vertical airflow. We will design and execute as the your requests.

 

  • In response to a request of the operating room, and then design and construction.
  • Airflow is selected from horizontal type and vertical type
  • Considering to the surgical operation

 

Model
BCO-4・2・A
Sterility
0.1 / ft or less
Class
ISO Class5 (Class 100)
Dust collection Effiency
More than 99.99% at 0.3μm
Dust collection elements
Main Filter: HEPA Filter, Pre Filter: Non-woven fabric filter
Air volume
Abt 200m³/min
Air Velocity
Abt  0.5m/sec
Noise
Abt  62dBA (1m from device)
Power supply
AC200V 3Φ 50/60Hz
Power Consumption
Abt  4200VA
Lighting
fluorescent lamp 40W×2
Weight
800kg
Construction
Body: Powder coated steel
Side panel: antistatic vinyl curtain and transparent PVC
Perforated plate: Anodized Alu plate
Wallboard: Stainless steel
Option
Sliding glass door, PVC panel

 

Danh mục sản phẩm